30kVA UPS w/o batteries

PMU-30

PMU series
New generation of ON-LINE double conversion digital UPS with DSP control
Advanced IGBT rectifier for low THD and high PF
PMU-30 30kVA UPS w/o batteries

Features

  • True online double conversion UPS with DSP control
  • High power density up to 200kVA
  • Superior overload capability
  • Unity power factor and low input distortion
  • Output power factor at 0.8 (0.9pf is customisable)
  • Wide input voltage and frequency windows
  • Parallel redundancy of up to 4 units
  • Includes internal Static and Manual bypass
  • Modular design allows for easy service and maintenance
  • Easy-to-operate LCD display for user-friendly operation
  • Eco mode for energy saving
  • Common or separate battery bank
  • Programmable battery voltage from 192Vdc to 240Vdc
  • Powerful charger built in
  • Intelligent charge modes with smart charge current adjustment
  • Programmable control and monitoring software via RS232
  • Versatile communication interface options for various applications
  • Megatec & MODBUS protocols supported

Applications:

  • Camera Surveillance
  • Gates
  • Telephone Systems
  • Computer
  • Servers
  • Point of Sale
  • Industrial
  • Medical
  • Mining
Login for pricing
SKU: 768030 Category:

PMU series
New generation of ON-LINE double conversion digital UPS with DSP control
Advanced IGBT rectifier for low THD and high PF
PMU-30 30kVA UPS w/o batteries

Model PMU-10 PMU-20 PMU-30 PMU-40 PMU-60 PMU-80 PMU-100 PMU-120 PMU-160 PMU-200
Capacity (VA) 10kVA 20kVA 30kVA 40kVA 60kVA 80kVA 100kVA 120kVA 160kVA 200kVA
Power Rating (W) 8kW 16kW 24kW 32kW 48kW 64kW 80kW 96kW 128kW 160kW
Input
Normal Voltage 380/400/415Vac, (3Ph + N+PE)
Voltage range 208-478Vac
Frequency Range 40-70Hz
Power Factor ≥0.99
Harmonic Distortion (THDi) 2% (100% non linear load)
Bypass Voltage Range Max. Voltage: +15% (optional +5%, +10%, +25%); Min. Voltage:-45% (optional -20%, -30%); Frequency protection range: ± 10%
Generator Input Supported
Output
Rated Voltage 380/400/415Vac, (3Ph+N+PE)
Power Factor 0.8/0.9(customisable)
Voltage Regulation ± 2%
Frequency Line mode: ± 1%/± 2%/±4%/±5%/±10% of the rated frequency (optional); Batt.mode: (50/60±0.2%)Hz
Crest factor 3:1
Harmonic distortion (THD) ≤2% with linear load,≤5% with non linear load
Efficiency 94,5% 95,5%
Battery
Battery voltage Standard unit: ±216Vdc; Long run unit optional voltage: ±192V/±204V/±216V/±228V/±240Vdc
Capacity ( standard unit) 12V/38Ah
Charge Current (A) Standard: 5.7A; Long Run: Max 6A Max 12A Max 18A Max 24A Max 30A Max 36A
System
Transfer time 0ms
Overload Line mode: load ≤ 110%: 60min; ≤125%: 10min; ≤150%: 1min; ≥150% shut down UPS immediately Batt. mode: load ≤ 110%: 10min; ≤125%: 1min; ≤150%: 5s; ≥150% shut down UPS immediately
Breaker 20A 40A 50A 80A 100A 125A 80A 100A 100A 125A
Short Circuit Hold whole system
Overheat Line mode: switch to bypass; backup mode: shut down UPS immediately
Low battery voltage Alarm and switch off
Self-diagnostics Shut down UPS immediately
Comms & Management
Ports RS232, RS485, Parallel, Intelligent slot, Relay card (optional), SNMP card (optional)
Software Windows 95/98/NT/2000/XP/Vista/7, Windows Server 2003/2008 Linux Debian, Redhat, Fedora, Suse, Ubuntu, CentOS, Novell, Mac, FreeBSD
LCD Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage & Inner Temperature
LED Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Options Harmonic filter, SNMP adapter, Battery temperature sensor, Manual Bypass
Environment
Operating temperature 0 – 40°C
Humidity 0 ~95% non-condensing
Storage temperature -25°C – 55°C
Noise Complies with EN62040-2
Physical characteristics
Net (kg) 123 125 126 164 166 195 286 317 348 355
Dimension (W x D x H) 600 x 780 x 1200 600 x 780 x 1600
Safety & EMC CE, EN/IEC 62040-2, EN/IEC 62040-1-1

Brand

PSS

Datasheet

Download

Data Sheet - PMU Combined - Trantech

Copyright © 2021 Trantech: Security Wholesaler. All Rights Reserved.