| Specifications | |||
| Model | XL+2000 | ||
| Capacity | 2KVA/1.6KW | ||
| Input | |||
| Voltage range | 177-300VAC | ||
| Frequency | 50 – 60Hz + / – 10% (Auto sensing) | ||
| Phase | Single phase | ||
| Max current Amps | 5A (10A Aus 3-Pin Plug) | 8A (10A Aus 3-Pin Plug) | 12A (15A Aus 3-Pin Plug) |
| Output | |||
| Output voltage | 220V, 230V, 240V LCD selectable | ||
| Output voltage regulation | Nominal Voltage + / – 5% | ||
| Frequency | 50 – 60 Hz + / – 0.1Hz | ||
| Wave form – AC mode | Pure sine wave | ||
| Wave form – battery mode | Pure sine wave – entire battery range | ||
| Transfer time | ≤6ms | ||
| Load crest factor | 3:1 | ||
| Outlets | 2 x 10A Aus, 1 x IEC | 3 x 10A Aus, 3 x IEC | 3 x 10A Aus, 3 x IEC |
| Battery | |||
| Battery type | Sealed maintenance free lead acid batteries | ||
| Number of batteries | 2 x 12V 7.5AH | 3 x 12V 9AH | 4 x 12V 9AH |
| Recharge time | 90% within 4 hours | ||
| Battery start | UPS can be started without an AC source | ||
| Automatic restart | Restart after battery low and mains returns | ||
| Protection | |||
| Surge protection | 1600 Joules / 40,000 Amps | ||
| Input protection | Compliance with IEEE 587 | ||
| Short circuit | Resettable circuit breaker | ||
| Safety & EMC | EN50091-1-1, EN50091-2, C Tick | ||
| Modem | RJ45, Full time network protection | ||
| Comms & Management | |||
| Software | Windows 95/98/NT/2000/XP/7, Windows Server 2003/2008 Linux Debian, Redhat, Fedora, Suse, Ubuntu, Centos, Novell, Mac, FreeBSD |
||
| Ports | USB standard | ||
| Optional | SNMP, RS232, Relay contact output, AS400 relay contact | ||
| LCD display | UPS status, I/P & O/P voltage frequency, load %, battery voltage & %, temperature, model | ||
| LED display | Normal (Green), back up (Yellow), fault (Red) | ||
| Audible alarm | Alarm – on battery, overload, short circuit, over temperature, abnormal operation | ||
| Characteristics | |||
| Audible noise | < 40dB at 1 Metre | ||
| Temperature & humidity | 0-40°C, 0-90% (non-condensing) | ||
| Ventilation | Fan forced front to back. Requires 50mm at the front and 150mm at the rear | ||
| Dimensions (WxDxH) / weight | 440x338x88(2RU)/12.2kg | 440x410x132(3RU)/21.3kg | 440x410x132(3RU)/26.7kg |
| Shipping dimensions / weight | 616x443x190/18kg | 545x545x245/24.5kg | 545x545x245/29.7kg |
| EBXL+ dimensions / weight | 440x468x88(2RU)/10-24kg | ||
| EBXL+ shipping dimensions / weight | 580x590x200/13-27kg | ||
2000VA Sine Wave Line-Interactive UPS
XL+2000
2000VA Sine Wave Line-Interactive UPS
Features
- Pure sinewave line interactive
- Rack/Tower conversion
- Auto restart (When mains returns)
- Smart management / Control software
- Lightening / surge protection and network protection
- Extendable Runtimes Via EBXL+ (extended battery module)
- Interactive LCD with Adjustable Settings
Applications
- Camera Surveillance
- Telephone Systems
- Computer
- Point of Sales
- Gates
- Servers
| Brand | PSS |
|---|