| Model | M15 |
| Capacity | 15KVA/12KW |
| Input | |
| Phase | 3 phase & Ground |
| Voltage Range | 400 or 415V ± 20% |
| Frequency | 50Hz ± 5% |
| Max. Current | 24A |
| Output | |
| Phase | Single Phase & Ground |
| Voltage Range | 230V ±1% |
| Wave Form | Sine wave |
| Frequency | 50Hz ±0.5% |
| THD (Linear Load) | <3% |
| Power Factor | 0,8 |
| Overload Capacity | Overload (110%-150%), 20s later go to bypass, automatically resume when load becomes normal |
| Short Circuit Protection | current limit, turn off automatically, switch protect |
| Communication | |
| Interface | RS232 |
| Battery | |
| DC Voltage | 192VDC |
| Max. Charge Current | 5A |
| Efficiency | |
| Whole Unit | 85%”}” data-sheets-textstyleruns=”{“1″:0,”2”:{“2”:{“1″:2,”2″:2301728},”3″:”Trebuchet MS”,”4″:9}}”>>85% |
| Transfer Time | |
| Mains to Inverter | 0ms |
| Panel Indication | |
| LCD | input/output voltage, input frequency, battery voltage, load capacity |
| LED | low battery, on-line, inverter, bypass, abnormal |
| Environment | |
| Temperature | 0-40 °C |
| Humidity | 0-90% (non-condensing) |
| Noise | <58dB |
| Other | |
| Net/Gross Weight (kg) | 262/302 |
| Dimensions (WxDxH)mm | 310 x 590 x 870 |
15kVA w/o batteries
M15
Master series
Double conversion ON-LINE with transformer
Intelligent RS-232 interface and static + manual bypass for critical installations
LCD and LED mimic panel. For medium size installations
Features
- Three phase in, one phase out
- True on-line double conversion design providing full power protection
- IGBT input voltage window
- Pure sine wave output with less than 3% THD
- Expandable backup run time
- Generator compatible
- Cold start
- Load/Battery power meter display
- Overload, on-line, battery status
- LED/LCD display
- Advanced Battery Management
- Automatically charging in UPS off mode
- Smart RS232 communication
- Optional SNMP card
Applications:
- Camera Surveillance
- Gates
- Telephone Systems
- Computer
- Servers
- Point of Sale
- Industrial
- Medical
- Mining
| Brand | PSS |
|---|